ZQ-CY Series Atmospheric Thermal Deaerator (4-35t/h)
Uses steam to heat boiler feedwater to 104°C, removing dissolved oxygen to ≤0.05mg/L, preventing boiler oxygen corrosion and extending boiler service life. Northeast China groundwater has high hardness and high oxygen content, making the deaerator a standard boiler room equipment.

产品特性
产品描述
ZQ-CY Series Atmospheric Thermal Deaerator
Dissolved oxygen is the primary cause of boiler corrosion. Northeast China groundwater has dissolved oxygen as high as 8-12mg/L, which will cause rapid perforation of furnace tubes if not removed. This series adopts a two-stage deaeration process combining rotary film and packing, achieving outlet oxygen content ≤0.05mg/L.
Process Principle
- Primary Deaeration (Rotary Film Tube): Feedwater forms a high-speed rotating water film, with steam penetrating in countercurrent direction, achieving 80% deaeration
- Secondary Deaeration (Stainless Steel Packing Layer): Deep mass transfer ensures compliance with standards
- Water Tank Storage: Equipped with steam reboiling tubes to prevent secondary oxygen dissolution
Specifications
| Model | Capacity | Tank Volume | Working Pressure | Applicable Boiler |
|---|---|---|---|---|
| ZQ-CY4 | 4t/h | 5m³ | Atmospheric | 1-4t/h |
| ZQ-CY10 | 10t/h | 10m³ | Atmospheric | 4-10t/h |
| ZQ-CY20 | 20t/h | 20m³ | Atmospheric | 10-20t/h |
| ZQ-CY35 | 35t/h | 35m³ | Atmospheric | 20-35t/h |
Northeast China Application: Groundwater in Harbin, Mudanjiang and other areas has hardness as high as 300-500mg/L. Combined with sodium ion softener after deaeration, boilers can be ensured to operate for 15 years without corrosion.